- The RV-K 0.6/1KV cable is used in low-voltage industrial installations, Underground distribution networks and outdoor wiring.
- Complies with IEC standards 60502-1 and offers increased resistance to chemical agents, in oil, UV and mechanical shocks.
- This cable is compatible with a direct buried installation, outdoors without additional protection, or in closed pipe.
Product description
The RV - K cable is a flexible low -voltage power cable (0,6/1 kV), intended for electrical distribution in industrial environments, Urban networks and buildings installations. Thanks to its great flexibility (Copper soul Class5), It is particularly suitable for complex or difficult to wire circuits. It can be buried, placed in chute or used outdoors without additional protection, with good water resistance (AD8 class, Permanent immersion up to 5m), oils, chemicals, shocks and UV. It complies with the IEC60502-1 and UN21123-2 standards, With XLPE insulation and flagship PVC exterior sheath (EN60332-1). Operating temperature : -15 ° C to +90 ° C, Curvon rays ≥5 × Outside diameter.
Construction of the RV-K cable
Element | Material / Specification |
Driver | Copper, multibrins, flexible class 5 (in accordance with IEC standard 60228 / From vde) |
Isolation | XLPE (cross-linked polyethylene), Thermal resistance up to 90 ° C |
Outer sheath | nursing PVC, flame (IN 60332-1), UV resistant, oils and chemicals |
Application
- Industrial production sites, Distribution stations and control cabinets
- Urban electrical networks, industrial installations and distribution in buildings
- Recessed installation (in conduits), apparent pose (chute), Buried and outdoor installation
- Complex wiring installations requiring great connection flexibility
Standard
EN60332-1, IEC 60332-1, IEC 60502-1, UN21123-2
RV-K cable settings
Standards | Complies with IEC standards 60502-1 and a 21123-2 |
Tension nominale | 0,6/1 kV (alternating current) ; 0,9/1,8 kV (direct current) |
Service temperature | From –15 ° C to +90 ° C ; up to +250 ° C in short circuit (maximum duration : 5 seconds) |
Minimal curvature radius | ≥ 5 times the outside diameter |
Tightness | AD8 - prolonged immersion possible up to 5m deep |
Fire behavior | Complies with the standard in 60332-1 (Flame propagation resistance) |
Technical data
Reference | Section (mm²) | Maximum resistance in C.C 20 ℃ (Ω/km) | Outside diameter Approx (mm) | Masse approx (Kg/km) | Eligible intensity in (A) AIX AIR 30 ℃ | Eligible intensity in (A) buried | Chute de Tension v/a/km cos∅ = 0.8 | Packaging standard |
1 Round copper driver
Rvk1.5 | 1×1.5 | 0.7 | 5.6 | 41 | 24 | 31 | 26 | T 3000 |
RVK2.5 | 1×2.5 | 0.7 | 6.0 | 55 | 33 | 41 | 15 | T 3000 |
Rvk4 | 1×4 | 0.7 | 6.5 | 75 | 45 | 53 | 10.2 | T 2000 |
Rvk6 | 1×6 | 0.7 | 7.3 | 100 | 58 | 66 | 6.83 | T 2000 |
Rvk10 | 1×10 | 0.7 | 8.0 | 140 | 80 | 87 | 4.06 | T 2000 |
RVK16 | 1×16 | 0.7 | 8.9 | 200 | 107 | 113 | 2.55 | T 1000 |
Rvk25 | 1×25 | 0.9 | 11.4 | 300 | 138 | 144 | 1.6 | T 1000 |
Rvk35 | 1×35 | 0.9 | 12.7 | 400 | 169 | 174 | 1.16 | T 1000 |
RVK50 | 1×50 | 1.0 | 14.5 | 535 | 207 | 206 | 0.86 | T 1000 |
RVK70 | 1×70 | 1.1 | 16.7 | 740 | 268 | 254 | 0.59 | T 1000 |
Rvk95 | 1×95 | 1.1 | 18.8 | 950 | 328 | 301 | 0.43 | T 1000 |
Rvk120 | 1×120 | 1.2 | 20.8 | 1200 | 382 | 343 | 0.34 | T 1000 |
RVK150 | 1×150 | 1.4 | 23.5 | 1500 | 441 | 387 | 0.27 | T 1000 |
Rvk185 | 1×185 | 1.6 | 25.5 | 1900 | 506 | 434 | 0.22 | T 1000 |
RVK240 | 1×240 | 1.7 | 28.8 | 2350 | 599 | 501 | 0.17 | T 500 |
RVK300 | 1×300 | 1.8 | 31.5 | 3000 | 693 | 565 | 0.13 | T 500 |
2 Round copper drivers
Rvkb1.5 | 2×1.5 | 0.7 | 9.5 | 100 | 26 | 37 | 31 | T 2000 |
RVKB2.5 | 2×2.5 | 0.7 | 10.5 | 120 | 36 | 48 | 19 | T 2000 |
RVKB4 | 2×4 | 0.7 | 11.5 | 170 | 49 | 63 | 11.8 | T 1000 |
RVKB6 | 2×6 | 0.7 | 12.5 | 250 | 63 | 80 | 7.9 | T 1000 |
RVKB10 | 2×10 | 0.7 | 14.5 | 330 | 86 | 104 | 4.7 | T 1000 |
RVKB16 | 2×16 | 0.7 | 16.5 | 510 | 115 | 136 | 2.8 | T 1000 |
RVKB25 | 2×25 | 0.9 | 21.5 | 800 | 149 | 173 | 1.8 | T 1000 |
RVKB35 | 2×35 | 0.9 | 24.0 | 1040 | 185 | 208 | 1.3 | T 1000 |
3 Triphase round copper drivers (2)
RVKC1.5 | 3G1.5 | 0.7 | 9.8 | 120 | 23 | 31 | 22 | T 2000 |
RVKC2.5 | 3G2.5 | 0.7 | 10.8 | 150 | 31 | 41 | 14 | T 1800 |
RVKC4 | 3G4 | 0.7 | 12.0 | 205 | 42 | 53 | 9.0 | T 1000 |
RVKC6 | 3×6 | 0.7 | 13.0 | 300 | 54 | 66 | 6.0 | T 1000 |
Rvkc10 | 3×10 | 0.7 | 15.5 | 460 | 75 | 87 | 3.4 | T 1000 |
RVKC16 | 3×16 | 0.7 | 17.5 | 650 | 100 | 113 | 2.3 | T 1000 |
RVKC25 | 3×25 | 0.9 | 22.5 | 1010 | 127 | 144 | 1.5 | T 1000 |
RVKC35 | 3×35 | 0.9 | 25.5 | 1350 | 158 | 174 | 1.1 | T 1000 |
RVKC50 | 3×50 | 1.0 | 29.3 | 1850 | 192 | 206 | 0.8 | T 1000 |
RVKC70 | 3×70 | 1.1 | 34.3 | 2500 | 246 | 254 | 0.6 | T 500 |
RVKC95 | 3×95 | 1.1 | 38.5 | 3450 | 298 | 301 | 0.45 | T 500 |
RVKC120 | 3×120 | 1.2 | 43.0 | 4400 | 346 | 343 | 0.38 | T 500 |
RVKC150 | 3×150 | 1.4 | 48.5 | 5400 | 395 | 387 | 0.32 | T 500 |
RVKC185 | 3×185 | 1.6 | 53.0 | 6500 | 450 | 434 | 0.26 | T 500 |
4 three -phase round copper drivers
Rvkd1.5 | 4G1.5 | 0.7 | 10.5 | 135 | 23 | 31 | 22 | T 1500 |
Rvkd2.5 | 4G2.5 | 0.7 | 12.0 | 180 | 31 | 41 | 14 | T 1000 |
Rvkd4 | 4G4 | 0.7 | 13.0 | 250 | 42 | 53 | 9.0 | T 1000 |
RVKD6 | 4×6 | 0.7 | 14.0 | 370 | 54 | 66 | 6.0 | T 1000 |
Rvkd10 | 4×10 | 0.7 | 16.5 | 570 | 75 | 87 | 3.4 | T 1000 |
RVKD16 | 4×16 | 0.7 | 19.0 | 815 | 100 | 113 | 2.3 | T 1000 |
Rvkd25 | 4×25 | 0.9 | 24.8 | 1300 | 127 | 144 | 1.5 | T 1000 |
Rvkd35 | 4×35 | 0.9 | 27.9 | 1680 | 158 | 174 | 1.1 | T 1000 |
RVKD50 | 4×50 | 1.0 | 32.5 | 2340 | 192 | 206 | 0.8 | T 1000 |
Rvkd70 | 4×70 | 1.1 | 38.0 | 3260 | 246 | 254 | 0.6 | T 500 |
Rvkd95 | 4x 95 | 1.1 | 42.8 | 4100 | 298 | 301 | 0.45 | T 500 |
RVKD120 | 4×120 | 1.2 | 48.1 | 5300 | 346 | 343 | 0.38 | T 500 |
3 drivers + Tribhase round copper neutral
RVKC5025 | 3×50+25 | 1.0/0.9 | 31.5 | 2100 | 192 | 206 | 0.86 | T 1000 |
Rvkc7035 | 3×70+35 | 1.1/0.9 | 36.5 | 2900 | 246 | 254 | 0.6 | T 1000 |
R0VC9550 | 3×95+50 | 1.1/1.0 | 41.5 | 3700 | 298 | 301 | 0.43 | T 500 |
RVKC12070 | 3×120+70 | 1.2/1.1 | 45.5 | 5200 | 346 | 343 | 0.34 | T 500 |
RVKC15070 | 3×150+70 | 1.4/1.1 | 51.5 | 6300 | 395 | 387 | 0.28 | T 500 |
RVKC18595 | 3×185+95 | 1.6/1.1 | 55.8 | 7800 | 450 | 434 | 0.22 | T 500 |
RVKC240120 | 3×240+120 | 1.7/1.2 | 64.5 | 9600 | 538 | 501 | 0.17 | T 250 |
5 Triphase round copper drivers
Rvke4 | Rvke4 | 0.7 | 14.0 | 290 | 45 | 37 | 11.0 | T 1000 |
Rvke6 | Rvke6 | 0.7 | 15.5 | 390 | 54 | 46 | 7.32 | T 1000 |
Rvke10 | Rvke10 | 0.7 | 18.0 | 655 | 75 | 61 | 4.23 | T 1000 |
Advantages of the RV-K cable made by ZMS Cable
Exceptional flexibility and ease of installation
Made with class copper drivers 5, RV-K cable is extremely flexible. It lends itself perfectly to the passages in conduits, tight curvatures and complex installations in industrial environments.
Excellent resistance to external conditions
Its PVC sheath offers great resistance to oils, chemicals and UV rays. It can be placed directly outdoors without additional protection.
Very good sealing
Classified AD8, This cable is suitable for wet environments and can be submerged in a prolonged way until 5 meters deep.
Fleaze design for increased safety
The outdoor sheath complies with the standard 60332-1 (IEC 60332-1), guaranteeing excellent resistance to flame propagation and improving fire safety.
Large temperature range and high short-circuit resistance
Reliable operation in a temperature range of –15 ° C to +90 ° C, with a short-circuit outfit that can reach +250 ° C for 5 seconds.
Guaranteed quality and compliance standards
ZMS ensures rigorous manufacturing quality control. RV-K cables comply with IEC standards 60502-1 and a 21123-2.
Technical comparison : Câble rv-k vs rz1-k vs rz1MZ1-k
Features / References | RV-K | Rz1-k (LSZH - Low smoke and halogen -free emission) | RZ1MZ1-K (Armed lszh) |
Driver | Multibrin copper, class 5 flexible | Multibrin copper, class 5 | Multibrin copper, class 5 |
Isolation | XLPE (cross-linked polyethylene) | XLPE | XLPE |
Outer sheath | PVC Ignifuge, resistant to oil and UV | LSZH | LSZH + steel band armor |
Environmental resistance | Chemical resistant, humidity (AD8) | Good chemistry, Best fire -to -fire | Very high mechanical resistance and fire |
Usage environment | Industrial, outside, buried pose | Interior, High safety requirement areas | High risk/exterior, buried pose |
Fire reaction standards | IN 60332-1 | IN 60332-1 + IEC 61034 (low smoke) | Identical to RZ1-K + mechanical protection |
Flexibility / curvature | Rayon ≥ 5ר, Excellent flexibility | Similar curvature | Less flexible, But usable in classic pose |
Examples of Applications | Industrial distribution, control cupboards, exterior | Data centers, gaines techniques, rescue | Technical chutes, elevators, Heavy mechanical equipment |
Recommendations
- RV-K : Economic and reliable solution for general industrial applications, outdoors or buried.
- Rz1-k : Recommended for installations where fire safety and smoke toxicity are priorities.
- RZ1MZ1-K : Ideal for mechanically binding environments or with high risks.
Packaging, delivery & personalization
Packaging
ZMS RV-K cables are delivered in wooden towns, Reinforced plastic or boxes, depending on the section and the length. The ends are sealed with bopp ribbon and anti-humidity caps.
Standard lengths available
Minimum command of 300 meters
Personalization service
- Section and number of custom drivers
- Cable marking according to specifications
- Choice of the color of the outer sheath
- CE certificates, RoHS, ISO provided on request
Similar products
- All Posts
- News
- Blog
- Electric cable types

RZ1-K and Rz1-K cable (AS) – Soft power cable LSZH 0.6/1 kV – 1,8/3 KV Fire resistant cables, Flower cables..

Cable RZ1MZ1-K 0.6/1 kV – Maximum Fire Safety without halogen, low smoke – Ideal for certified public places..

Aluminum cable 0.6/1KV electric RV-Al cable LXV Low voltage supplier supplier Aluminum Cable Electric cable for fixed installation Low cable..

Low voltage industrial cables Tüv, CE, RoHS, NF C 32-321, IN 60228 Multibrical tinned copper driver, isolation XLPE, sheath...

H07RN-F cable – High performance rubber cable cable in high flexibility oil resistant flexibility, Ozone and ...