NHXH and NHXCH cables



- Halogen-free power cables, fire -resistant (FE180/E30, FE180/E90), U0/U 0,6/1 kV, copper conductors – suitable for fixed security installations.
- Special halogen-free insulation and sheathing : low smoke and toxic gas emissions to protect people and sensitive equipment.
- Excellent fire resistance : maintaining the integrity of the insulation and electrical operation during 30 has 90 minutes depending on configuration.
- Compliant with IEC standards 60331, IN 50200
- Available in armored version (Socialist Republic of Vietnam) with concentric conductor for electromagnetic protection and improved grounding.
- Custom manufacturing by ZMS CABLE : sections, lengths and packaging adapted to your needs.
What is NHXH cable and NHXCH cable ?
NHXH and NHXCH cables are halogen-free power and control cables, specially designed to guarantee the safety of electrical installations in the event of fire. Complies with European standards and classification FE180/E30-E90, they ensure, even during a fire, integrity of insulation and maintenance of function for a defined period of time.
NHXH cable is the standard version, unshielded, ideal for electrical networks in public buildings, Hospitals, train stations or industrial sites. The NHXCH cable, as for him, incorporates copper shielding for effective protection against electromagnetic interference, making it ideally suited to sensitive environments such as data centers or industrial control systems.
Construction


| Features | NHXH cable – FE180/E30 | NHXH cable – FE180/E90 | NHXCH cable – FE180/E30 | NHXCH cable – FE180/E90 |
| Tension nominale | 0,6/1 kV | |||
| Driver | Copper class 1 (< 25 mm²) Copper class 2 (≥ 25 mm²) | |||
| Isolation | Halogen-free polymer with flame-resistant mica tape | |||
| Internal sheath | Halogen-free compound | |||
| Concentric conductor | – | Concentric copper wires with helical copper tape | ||
| Outer sheath | Halogen-free polymer | |||
Application of NHXH cables & Socialist Republic of Vietnam
- Fire safety installations (automatic detection and extinguishing systems)
- Emergency lighting and power supply for emergency exits
- Fire alarm and emergency communications systems
- Elevators and emergency ventilation guaranteeing safe evacuation
- Sensitive public environments : hospitals, schools, stations, airports
- Tunnels and transport infrastructures requiring reliable power even in the event of a disaster
Standard
| NHXH and NHXCH – FE180 – E30 / E90 | |
| Flame retardant | VDE 0482-266-2-4 / IEC 60332-3-24 |
| Smoke density | YOUR ONE 61034 / IEC 61034 |
| Halogen-free | YOUR ONE 50267 / IEC 60754 |
| Fire resistant insulation | FE 180 (Compliant with IEC 60331) FE 180 : integrity of the insulation guaranteed during 180 minutes in direct contact with flames |
| Circuit integrity | Available in E30 / E90 – E30 : guarantees the operation of electrical circuits for at least 30 minutes during a fire. – E90 : guarantees operation for at least 90 minutes, ideal for critical systems (fire pumps, emergency ventilation). |
Technical parameters of NHXH and NHXCH cables (0,6/1 kV)
| Tension nominale | 0,6/1 kV |
| Test voltage | 4 kV (AC) |
| Installation temperature | –5°C to +50 °C |
| Operating temperature | –35°C to +90 °C |
| Short-circuit temperature (max.) | Until 250 °C |
| Minimum bending radius. (fixed) | Monoconductor : 15ר Multiconductor : 12ר |
Technical data
IN 60332-3-24 NHXH FE180-E90 0.6/1kV Cable
| Number of drivers | Nominal section (mm²) | Driver type | Nominal external diameter (mm) | Poids nominal (kg/km) |
| 1 | 16 | RM | 10.5 | 250 |
| 1 | 25 | RM | 12.5 | 355 |
| 1 | 35 | RM | 13.5 | 460 |
| 1 | 50 | RM | 15 | 596 |
| 1 | 70 | RM | 16.5 | 810 |
| 1 | 95 | RM | 19 | 1100 |
| 1 | 120 | RM | 20.5 | 1350 |
| 1 | 150 | RM | 22.5 | 1650 |
| 1 | 185 | RM | 25 | 2050 |
| 1 | 240 | RM | 28 | 2650 |
| 1 | 300 | RM | 31 | 3275 |
| 2 | 1.5 | RE | 14.3 | 275 |
| 2 | 2.5 | RE | 14.9 | 320 |
| 3 | 1.5 | RE | 15 | 315 |
| 3 | 2.5 | RE | 15.9 | 371 |
| 3 | 4 | RE | 16.7 | 435 |
| 3 | 6 | RE | 17.8 | 526 |
| 3 | 10 | RE | 19.5 | 691 |
| 3 | 16 | RM | 22.3 | 982 |
| 3 | 25 | RM | 25.8 | 1392 |
| 3 | 35 | RM | 28.4 | 1778 |
| 3 | 35/16 | RM | 29.5 | 1964 |
| 3 | 50/25 | RM | 33.6 | 2633 |
| 3 | 70/35 | RM | 38.1 | 3563 |
| 3 | 95/50 | RM | 43.4 | 4768 |
| 3 | 120/70 | RM | 46.9 | 5856 |
| 4 | 1.5 | RE | 16.1 | 365 |
| 4 | 2.5 | RE | 17 | 429 |
| 4 | 4 | RE | 18 | 515 |
| 4 | 6 | RE | 19.2 | 628 |
| 4 | 10 | RE | 21.1 | 839 |
| 4 | 16 | RE | 24.3 | 1210 |
| 4 | 25 | RM | 28.1 | 1717 |
| 4 | 35 | RM | 31 | 2209 |
| 4 | 50 | RM | 35.1 | 2921 |
| 4 | 70 | RM | 40 | 3980 |
| 4 | 95 | RM | 45.2 | 5321 |
| 4 | 120 | RM | 49 | 6475 |
| 4 | 150 | RM | 53 | 7725 |
| 5 | 1.5 | RE | 17.4 | 429 |
| 5 | 2.5 | RE | 18.4 | 506 |
| 5 | 4 | RE | 19.5 | 612 |
| 5 | 6 | RE | 20.9 | 752 |
| 5 | 10 | RE | 23 | 1009 |
| 5 | 16 | RM | 26.6 | 1465 |
| 5 | 25 | RM | 30.9 | 2105 |
| 5 | 35 | RM | 36 | 2500 |
IN 60332-3-24 NHXH FE180-E30 0.6/1kV Cable
| Number of drivers | Nominal section (mm²) | Driver type | Nominal external diameter (mm) | Poids nominal (kg/km) |
| 1 | 16 | RM | 18.6 | 207 |
| 1 | 25 | RM | 20.6 | 307 |
| 1 | 35 | RM | 22.8 | 407 |
| 1 | 50 | RM | 26.3 | 535 |
| 1 | 70 | RM | 30 | 744 |
| 1 | 95 | RM | 10.2 | 1009 |
| 1 | 120 | RM | 18.6 | 1248 |
| 1 | 150 | RM | 20.6 | 1538 |
| 1 | 185 | RM | 22.8 | 1917 |
| 1 | 240 | RM | 26.3 | 2521 |
| 1 | 300 | RM | 30 | 3400 |
| 2 | 1.5 | RE | 10.2 | 145 |
| 2 | 2.5 | RE | 11 | 180 |
| 2 | 4 | RE | 11.8 | 224 |
| 2 | 6 | RE | 12.8 | 282 |
| 2 | 10 | RE | 14.4 | 393 |
| 2 | 16 | RM | 17.3 | 605 |
| 3 | 1.5 | RM | 10.6 | 165 |
| 3 | 2.5 | RM | 11.5 | 209 |
| 3 | 4 | RM | 12.4 | 268 |
| 3 | 6 | RM | 13.5 | 344 |
| 3 | 10 | RM | 15.6 | 506 |
| 3 | 16 | RM | 18 | 761 |
| 3 | 25 | RM | 22.3 | 1160 |
| 3 | 35 | RM | 24.9 | 1522 |
| 3 | 50 | RM | 27.7 | 198 |
| 3 | 70 | RM | 32 | 2746 |
| 3 | 95 | RM | 36.5 | 3712 |
| 3 | 25/16 | RM | 23.4 | 1335 |
| 3 | 35/16 | RM | 25.7 | 1683 |
| 3 | 50/25 | RM | 29 | 2244 |
| 3 | 70/35 | RM | 33.4 | 3101 |
| 3 | 95/50 | RM | 38.3 | 4207 |
| 3 | 120/70 | RM | 42.6 | 5315 |
| 4 | 1.5 | RE | 11.3 | 192 |
| 4 | 2.5 | RE | 12.3 | 249 |
| 4 | 4 | RE | 13.3 | 322 |
| 4 | 6 | RE | 14.5 | 418 |
| 4 | 10 | RE | 16.8 | 620 |
| 4 | 16 | RM | 19.8 | 944 |
| 4 | 25 | RM | 24.3 | 1452 |
| 4 | 35 | RM | 27.1 | 1906 |
| 4 | 50 | RM | 30.5 | 2514 |
| 4 | 70 | RM | 35.3 | 3497 |
| 4 | 95 | RM | 40.2 | 4728 |
| 4 | 120 | RM | 44.5 | 5882 |
| 4 | 150 | RM | 49 | 7199 |
IN 60332-3-24 NHXCH FE180-E90 0.6/1kV Cable
| Number of drivers | Nominal section (mm²) | Driver type | Concentric conductor diameter (mm) | Nominal external diameter (mm) | Poids nominal (kg/km) |
| 2 | 1.5 | RE | 1.5 | 16 | 300 |
| 2 | 2.5 | RE | 2.5 | 17 | 350 |
| 3 | 1.5 | RE | 1.5 | 16.8 | 363 |
| 3 | 2.5 | RE | 2.5 | 17.9 | 434 |
| 3 | 4 | RE | 4 | 19 | 434 |
| 3 | 6 | RE | 6 | 21 | 434 |
| 3 | 10 | RE | 10 | 24.1 | 949 |
| 3 | 16 | RE | 16 | 27.3 | 1340 |
| 3 | 25 | RM | 16 | 30.7 | 1766 |
| 3 | 35 | RM | 16 | 33.3 | 2172 |
| 3 | 50 | RM | 25 | 37.4 | 2857 |
| 3 | 70 | RM | 35 | 42.5 | 3839 |
| 3 | 95 | RM | 50 | 47.8 | 5082 |
| 3 | 120 | RM | 70 | 51.4 | 6204 |
| 3 | 150 | RM | 70 | 55.7 | 7340 |
| 3 | 185 | RM | 95 | 61.7 | 9142 |
| 3 | 240 | RM | 120 | 67.9 | 11582 |
| 4 | 1.5 | RE | 1.5 | 18 | 450 |
| 4 | 2.5 | RE | 2.5 | 19.2 | 505 |
| 4 | 4 | RE | 4 | 20.3 | 608 |
| 4 | 6 | RE | 6 | 22.5 | 777 |
| 4 | 10 | RE | 10 | 26.4 | 1153 |
| 4 | 16 | RM | 16 | 29.3 | 1584 |
| 4 | 25 | RM | 16 | 33.1 | 2120 |
| 4 | 35 | RM | 16 | 36 | 2634 |
| 4 | 50 | RM | 25 | 41.1 | 3524 |
| 4 | 70 | RM | 35 | 46.2 | 4695 |
| 4 | 95 | RM | 50 | 52 | 6242 |
| 4 | 120 | RM | 70 | 56 | 7622 |
| 4 | 150 | RM | 70 | 61 | 9096 |
| 4 | 185 | RM | 95 | 67.5 | 11307 |
| 4 | 240 | RM | 120 | 74.4 | 14359 |
| 7 | 1.5 | RE | 2.5 | 20.9 | 588 |
| 7 | 2.5 | RE | 2.5 | 22.1 | 696 |
| 12 | 1.5 | RE | 2.5 | 26.2 | 620 |
| 12 | 2.5 | RE | 2.5 | 28.2 | 1168 |
| 24 | 1.5 | RE | 6 | 37.6 | 1979 |
| 24 | 2.5 | RE | 2.5 | 41 | 2465 |
IN 60332-3-24 NHXCH FE180-E30 0.6/1kV Cable
| Number of drivers | Nominal section (mm²) | Driver type | Concentric conductor diameter (mm) | Nominal external diameter (mm) | Poids nominal (kg/km) |
| 2 | 1.5 | RE | 1.5 | 10.8 | 133 |
| 2 | 2.5 | RE | 2.5 | 12 | 171 |
| 3 | 1.5 | RE | 1.5 | 11.2 | 166 |
| 3 | 2.5 | RE | 2.5 | 12.5 | 219 |
| 3 | 4 | RE | 4 | 13.4 | 291 |
| 3 | 6 | RE | 6 | 15.3 | 393 |
| 3 | 10 | RE | 10 | 17 | 576 |
| 3 | 16 | RE | 16 | 19.6 | 860 |
| 3 | 25 | RM | 16 | 23 | 1194 |
| 3 | 35 | RM | 16 | 25.6 | 1521 |
| 3 | 50 | RM | 25 | 28.8 | 2037 |
| 3 | 70 | RM | 35 | 33.7 | 2841 |
| 3 | 95 | RM | 50 | 38.2 | 384 |
| 3 | 120 | RM | 70 | 42.3 | 4869 |
| 3 | 150 | RM | 70 | 46.6 | 5844 |
| 3 | 185 | RM | 95 | 52.3 | 7400 |
| 3 | 240 | RM | 120 | 59.7 | 9661 |
| 4 | 1.5 | RE | 1.5 | 11.9 | 192 |
| 4 | 2.5 | RE | 2.5 | 13.3 | 254 |
| 4 | 4 | RE | 4 | 14.3 | 341 |
| 4 | 6 | RE | 6 | 16.3 | 471 |
| 4 | 10 | RE | 10 | 18.2 | 685 |
| 4 | 16 | RM | 16 | 21.1 | 1035 |
| 4 | 25 | RM | 16 | 25 | 1465 |
| 4 | 35 | RM | 16 | 27.8 | 1886 |
| 4 | 50 | RM | 25 | 31.6 | 2539 |
| 4 | 70 | RM | 35 | 37 | 3556 |
| 4 | 95 | RM | 50 | 41.9 | 4816 |
| 4 | 120 | RM | 70 | 46.6 | 6101 |
| 4 | 150 | RM | 70 | 51.1 | 7323 |
| 4 | 185 | RM | 95 | 57.6 | 9285 |
| 4 | 240 | RM | 120 | 65.8 | 12141 |
| 5 | 2.5 | RE | 2.5 | 14.3 | 283 |
| 5 | 6 | RE | 6 | 17.5 | 530 |
| 7 | 1.5 | RE | 2.5 | 14.2 | 274 |
| 7 | 2.5 | RE | 2.5 | 15.4 | 348 |
| 12 | 1.5 | RE | 2.5 | 17.4 | 399 |
| 12 | 2.5 | RE | 4 | 19.2 | 556 |
| 24 | 1.5 | RE | 6 | 23.7 | 744 |
| 24 | 2.5 | RE | 10 | 26.1 | 1027 |
| 30 | 1.5 | RE | 6 | 24.8 | 873 |
| 30 | 2.5 | RE | 10 | 27.4 | 1216 |
Advantages of NHXH cables & Socialist Republic of Vietnam
- Fire resistant : Certification FE180/E30 et FE180/E90, guaranteeing the maintenance of the electrical function during 30 has 90 minutes in case of fire.
- Halogen-free and low smoke : Limitation of toxic and corrosive gases to protect sensitive people and equipment.
- Increased security : Risk reduction in emergencies, ensuring the continuity of critical systems.
- Compliance with European standards : Manufactured according to IEC 60331 and in 50200, guarantee of quality and reliability.
- Adapted to demanding environments : Suitable for both public infrastructures and industrial sites with a high level of security.
- Tailor-made solutions : ZMS CABLE offers custom design and manufacturing of NHXH and NHXCH cables to your specific needs
Services & Delivery at ZMS Cable
- Personalized manufacturing service (OEM / ODM) : Custom cable design and production according to your technical specifications, with customization of the marking, Colors and packaging.
- Rapid global logistics : Shipping shipping, terrestrial or air to more than 120 pays ; Flexible delivery according to your deadlines.
- Certified quality : All products are tested before shipping ; conformity this / IEC / ISO ; test reports provided on request.
- Neat and customizable packaging : ZMS cables are packaged on wooden coils, wavy boxes or drums, with hermetically sealed ends for moisture protection. Outdoor marking can be printed on request with waterproof materials.
- Dedicated technical support : Our engineers and advisers accompany you in the choice of the electric cable most suited to your installations, in accordance with local standards.