- Maximum security : The N2XH cable is a low voltage cable 0,6/1 KV designed for fixed installations requiring high fire protection.
- Halogen-free (LSZH) : LSZH insulation and sheath, low smoke emission and no corrosive gas in the event of a fire, Fire safety, NORME IEC
- Quality copper driver : High conductivity, low resistance, lifetime.
- Pose flexible : Ideal for tunnels, public buildings, hospitals, Data centers and sensitive infrastructure.
- Compliant with standards : Manufacturing according to VDE, IEC, and CPR requirements for certified security.
Product description
The N2XH cable is a low voltage cable (0,6/1 kV) Designed for a fixed installation. It is a halogen -free cable (LSZH) smoke, specially developed to offer optimal fire safety. Thanks to its fire resistance and its low corrosivity of smoke (compliance IEC 60754-2), The N2XH cable effectively protects people and equipment in the event of a fire. It is perfectly suited to buildings with high occupation density, critical infrastructure and high -risk environments. Ideal for hospitals, data centers, Tunnels or public buildings, It can be placed on cable paths, conduit, in concrete or on wall, But is not suitable for direct burial without mechanical protection.
Construction

Part | Material / Type | Main function |
Driver | No, massif (class 1 ≤ 16 mm²) Ou Toron (class 2 ≥ 16 mm²) | Ensures the conduction of the current with low resistance |
Isolation | XLPE reticulated polyethylene, halogen-free, flame delayer | Electrical separation, Excellent thermal resistance |
Trim / Filling | Polypropylene wire and halogen -free filling strip (To maintain the round shape of multiconductive conductors) | Maintains the stable structure, prevents the crushing of souls |
Inner sheath | Compound LSZH-FRNC (halogen-free, low smoke) | Additional protection, strengthens fireproof performance |
Outer sheath | LSZH-FRNC material, generally black | Resist with fire, to corrosion, Compliant with fire safety requirements |
Armor (optional) | Monoconductor : Armure Aluminum hour ; multiconductor : Wire steel armor or Swiss/Sta band | Strengthens mechanical protection according to the installation environment |
Strengths and advantages
- All layers of insulation and sheath are made of LSZH materials (Low Smoke Zero Halogen) and frnc (Flame Retardant Non Corrosive), guaranteeing a low smoke emission and the absence of corrosive gas in the event of a fire, for optimal protection of people and equipment.
- A clear and controlled structure ensures excellent electrical performance, high quality of installation and reinforced security.
- The armor is optional as needed : For a standard interior installation, No armor is necessary ; for environments requiring increased mechanical protection, Armor in wires or steel strips is available.
N2XH cable applications
The N2XH cable (0,6/1 kV) is designed for fixed installations requiring reinforced fire safety thanks to its LSZH properties (halogen-free, low smoke) and at its fire resistance.
Recommended areas of application
- Fixed interior installations, on cable path, under plaster, built -in in concrete or on the walls.
- Public buildings and high density places of people : hospitals, schools, shopping centers, hotels, stations, airports, offices.
- Critical infrastructure : data centers, Electric stations, industrial central, transport networks.
- Tunnels, metros, underground parking lots where prevention of toxic smoke is essential.
Conditions of use and precautions
- No direct burial without mechanical protection or installation in water
- External installation authorized only in sheaths or conduits protecting from UV and bad weather
Standard
IEC 60502‑1, IEC 60754‑2, IEC 60332‑3‑24, IEC 61034, VDE 0276‑604, CPR / EN50575, RoHS, REACH
Settings
Setting | Value |
Nominal tension uo / u | 0,6/1 kV |
Operating temperature | Fixe : –30 ° C to +90 ° C (courant : –40 ° C to +90 ° C) |
Short-circuit temperature | Max. +250 °C (pendant ≤5 s) |
Minimum installation temperature | –5 °C |
AC test voltage | 2,5–4 kV |
Minimal curvature radius | Pose : 15×D (mono -soul), 12×D (multi -soul) ; Fixe : 10×D |
Driver range of sections | 1,5–630 mm² (single conductor) ; Multi -seas up to 300mm² |
XLPE insulation thickness | 0,7–2,2 mm |
LSZH exterior sheath thickness | 1,2–2,0 mm |
Outer diameter | ≈5,2–54 mm, according to section |
Approximate weight | 40 –10000kg/km, according to section |
Technical data
Mono-private cables
Nominal section (mm²) | Driver | Maximum resistance at 20 ° C (Ω/km) | Air admissible intensity (A) | Eligible intensity in the ground (A) | Outer diameter (approx.) (mm) | Metal weight (kg/km) | Cable weight (approx.) (kg/km) |
1×10 | RE/RM | 1,830 | 99 | 136 | 7,4 | 96 | 141 |
1x1g | RE/RM | 1,150 | 131 | 176 | 8,3 | 154 | 205 |
1×25 | RM | 0,727 | 177 | 229 | 9,8 | 240 | 307 |
1×35 | RM | 0,524 | 217 | 275 | 10,9 | 336 | 412 |
1×50 | RM | 0,387 | 265 | 326 | 12,4 | 480 | 571 |
1×70 | RM | 0,268 | 336 | 400 | 14,0 | 672 | 780 |
1×95 | RM | 0,193 | 415 | 480 | 15,8 | 912 | 1041 |
1×120 | RM | 0,153 | 485 | 548 | 17,4 | 1152 | 1300 |
1×150 | RM | 0,124 | 557 | 616 | 19,2 | 1440 | 1613 |
1×185 | RM | 0,0991 | 646 | 698 | 21,3 | 1776 | 1989 |
1×240 | RM | 0,0754 | 774 | 815 | 23,7 | 2304 | 2549 |
1×300 | RM | 0,0601 | 901 | 927 | 26,1 | 2880 | 3169 |
1×400 | RM | 0,0470 | 1060 | 1064 | 29,6 | 3840 | 4186 |
1×500 | RM | 0,0366 | 1252 | 1227 | 32,8 | 4800 | 5216 |
1×630 | RM | 0,0283 | 1486 | 1421 | 36,5 | 6048 | 6547 |
Cables 2 drivers
Nominal section (mm²) | Driver | Maximum resistance at 20 ° C (Ω/km) | Air admissible intensity (A) | Eligible intensity in the ground (A) | Outer diameter (approx.) (mm) | Metal weight (kg/km) | Cable weight (approx.) (kg/km) |
2×1,5 | RE/RM | 12,1 | 24 | 31 | 8,9 | 28,8 | 150 |
2×2,5 | RE/RM | 7,41 | 32 | 40 | 9,7 | 48,0 | 190 |
2×4 | RE/RM | 4,610 | 42 | 52 | 10,8 | 76,8 | 246 |
2×6 | RE/RM | 3,080 | 53 | 64 | 11,8 | 115,2 | 313 |
2×10 | RE/RM | 1,830 | 74 | 86 | 14,4 | 192,0 | 441 |
2×16 | RM | 1,150 | 98 | 112 | 16,5 | 307,2 | 620 |
2×25 | RM | 0,727 | 133 | 145 | 20,0 | 480,0 | 919 |
2×35 | RM | 0,524 | 162 | 174 | 22,5 | 672,0 | 1211 |
2×50 | RM | 0,387 | 197 | 206 | 25,1 | 960,0 | 1672 |
2×70 | RM | 0,268 | 250 | 254 | 28,8 | 1344,0 | 2247 |
2×95 | RM | 0,193 | 308 | 305 | 32,5 | 1824,0 | 2932 |
Cables 3 drivers
Nominal section (mm²) | Driver | Maximum resistance at 20 ° C (Ω/km) | Air admissible intensity (A) | Eligible intensity in the ground (A) | Outer diameter (approx.) (mm) | Metal weight (kg/km) | Cable weight (approx.) (kg/km) |
3×1,5 | RE/RM | 12,1 | 24 | 31 | 9,3 | 43,2 | 139,6 |
3×2,5 | RE/RM | 7,41 | 32 | 40 | 10,3 | 72 | 185,6 |
3×4 | RE/RM | 4,610 | 42 | 52 | 11,4 | 115 | 350 |
3×6 | RE/RM | 3,080 | 53 | 64 | 16,0 | 173 | 420 |
3×10 | RE/RM | 1,830 | 74 | 86 | 18,0 | 288 | 600 |
3×16 | RM | 1,150 | 98 | 112 | 20,0 | 461 | 770 |
3×25 | RM | 0,727 | 133 | 145 | 21,8 | 720 | 1120 |
3×35 | RM | 0,524 | 162 | 174 | 24,9 | 1008 | 1550 |
3×50 | RM | 0,387 | 197 | 206 | 25,2 | 1440 | 1982 |
3×70 | RM | 0,268 | 250 | 254 | 28,1 | 2016 | 2698 |
3×95 | RM | 0,193 | 308 | 305 | 31,7 | 2736 | 3592 |
3×120 | RM | 0,153 | 359 | 348 | 35,3 | 3456 | 4484 |
3×150 | RM | 0,124 | 412 | 392 | 39,3 | 4320 | 5571 |
3×185 | RM | 0,0991 | 475 | 444 | 43,6 | 5328 | 6876 |
3×240 | RM | 0,0754 | 564 | 517 | 49,0 | 6912 | 8799 |
3×50 | SM | 0,387 | 197 | 206 | 25,2 | 1440 | 1750 |
3×70 | SM | 0,268 | 250 | 254 | 29,2 | 2016 | 2450 |
3×95 | SM | 0,193 | 308 | 305 | 32,0 | 2736 | 3250 |
3×120 | SM | 0,153 | 359 | 348 | 34,9 | 3456 | 4000 |
3×150 | SM | 0,124 | 412 | 392 | 39,2 | 4320 | 5000 |
3×185 | SM | 0,0991 | 475 | 444 | 44,1 | 5328 | 6150 |
3×240 | SM | 0,0754 | 564 | 517 | 49,2 | 6912 | 8000 |
Cables 4 drivers
Nominal section (mm²) | Driver | Maximum resistance at 20 ° C (Ω/km) | Air admissible intensity (A) | Eligible intensity in the ground (A) | Outer diameter (approx.) (mm) | Metal weight (kg/km) | Cable weight (approx.) (kg/km) |
4×1,5 | RE/RM | 12,1 | 24 | 31 | 10,1 | 57,6 | 164,4 |
4×2,5 | RE/RM | 7,41 | 32 | 40 | 11,1 | 96 | 221,7 |
4×4 | RE/RM | 4,610 | 42 | 52 | 15,0 | 154 | 370 |
4×6 | RE/RM | 3,080 | 53 | 64 | 16,0 | 230 | 470 |
4×10 | RE/RM | 1,830 | 74 | 86 | 18,0 | 384 | 670 |
4×16 | RM | 1,150 | 98 | 112 | 20,0 | 614 | 930 |
4×25 | RM | 0,727 | 133 | 145 | 25,0 | 960 | 1440 |
4×35 | RM | 0,524 | 162 | 174 | 25,2 | 1344 | 1816 |
4×50 | RM | 0,387 | 197 | 206 | 28,2 | 1920 | 2513 |
4×70 | RM | 0,268 | 250 | 254 | 32,9 | 2688 | 3467 |
4×95 | RM | 0,193 | 308 | 305 | 37,2 | 3648 | 4579 |
4×120 | RM | 0,153 | 359 | 348 | 41,3 | 4608 | 5724 |
4×150 | RM | 0,124 | 412 | 392 | 45,8 | 5760 | 7158 |
4×185 | RM | 0,0991 | 475 | 444 | 50,6 | 7104 | 8785 |
4×240 | RM | 0,0754 | 564 | 517 | 57,6 | 9216 | 11310 |
4×35 | SM | 0,524 | 162 | 174 | 27,0 | 1344 | 1890 |
4×50 | SM | 0,387 | 197 | 206 | 28,0 | 1920 | 2300 |
4×70 | SM | 0,268 | 250 | 254 | 32,0 | 2688 | 3200 |
4×95 | SM | 0,193 | 308 | 305 | 36,0 | 3648 | 4250 |
4×120 | SM | 0,153 | 359 | 348 | 40,2 | 4608 | 5350 |
4×150 | SM | 0,124 | 412 | 392 | 44,8 | 5760 | 6550 |
4×185 | SM | 0,0991 | 475 | 444 | 49,5 | 7104 | 8100 |
4×240 | SM | 0,0754 | 564 | 517 | 56,0 | 9216 | 10550 |
Cables 5 drivers
Nominal section (mm²) | Driver | Maximum resistance at 20 ° C (Ω/km) | Air admissible intensity (A) | Eligible intensity in the ground (A) | Outer diameter (approx.) (mm) | Metal weight (kg/km) | Cable weight (approx.) (kg/km) |
5×1,5 | RE | 12,1 | 24 | 31 | 10,8 | 72 | 204 |
5×2,5 | RE | 7,41 | 32 | 40 | 11,8 | 120 | 272 |
5×4 | RE | 4,610 | 42 | 52 | 13,2 | 192 | 371 |
5×6 | RE | 3,080 | 53 | 64 | 14,6 | 288 | 496 |
5×10 | RE/RM | 1,830 | 74 | 86 | 16,9 | 480 | 737 |
5×16 | RE/RM | 1,150 | 98 | 112 | 19,4 | 768 | 1084 |
5×25 | RM | 0,727 | 133 | 145 | 23,6 | 1200 | 1641 |
5×35 | RM | 0,524 | 162 | 174 | 26,7 | 1680 | 2211 |
5×50 | RM | 0,387 | 197 | 206 | 30,9 | 2400 | 3076 |
5×70 | RM | 0,268 | 250 | 254 | 35,4 | 3360 | 4240 |
5×95 | RM | 0,193 | 308 | 305 | 39,9 | 4560 | 5617 |
5×120 | RM | 0,153 | 359 | 348 | 44,4 | 4608 | 5786 |
5×150 | RM | 0,124 | 412 | 392 | 49,9 | 5760 | 7237 |
Control cables
Nominal section (mm²) | Driver | Maximum resistance at 20 ° C (Ω/km) | Air admissible intensity (A) | Eligible intensity in the ground (A) | Outer diameter (approx.) (mm) | Metal weight (kg/km) | Cable weight (approx.) (kg/km) |
7×1,5 | RE | 12,1 | 24 | 31 | 12,5 | 100,8 | 231 |
7×2,5 | RE | 7,41 | 32 | 40 | 13,8 | 168,0 | 319 |
7×4 | RM/RE | 4,610 | 42 | 52 | 16,7 | 268,8 | 486 |
7×6 | RM/RE | 3,080 | 53 | 64 | 18,3 | 403,2 | 653 |
7×10 | RM/RE | 1,150 | 74 | 86 | 19 | 672,0 | 939 |
19×1,5 | RE | 12,1 | 24 | 31 | 17,4 | 273,6 | 450 |
19×2,5 | RE | 7,41 | 32 | 40 | 19,4 | 456,0 | 660 |
27×1,5 | RE | 12,1 | 24 | 31 | 20,8 | 388,8 | 628 |
27×2,5 | RE | 7,41 | 32 | 40 | 23,3 | 648,0 | 926 |
37×1,5 | RE | 12,1 | 24 | 31 | 23,2 | 532,8 | 831 |
37×2,5 | RE | 7,41 | 32 | 40 | 26,2 | 888,0 | 1246 |
Why choose the N2XH cable of ZMS Cable ?
- Certified quality : Manufacturing according to VDE and IEC standards, Strict quality control.
- Optimal security : LSZH, low smoke, Excellent fire resistance.
- Installation facile : Practical design for quick and reliable installation.
- Tailor -made service : Customizable sections and armor according to your project.
- Sustainable reliability : High -end materials, long -term stable performance.
Transport – ZMS CABLE
- The cables are packed on treated wooden towns or metal drums, With plastic film or BOPP for humidity protection.
- We offer maritime transport in 20ft or 40ft container, Depending on the control volume.
- Land transport is available for regional or local deliveries (Depending on the destinations).
- On demand, We also provide air transport for urgent orders.
- All necessary export documents are provided : commercial invoice, packing list, original certificate, documents douaniers, etc.